10 3N·mm/(1204* 10 3mm 3)=149.82 N/mm 2 =149.82 MPa <[σ]=215 MPa 横梁承受的剪切应力τ 1=V/A=180372N /(117.84* 10 2mm 2)=15.31N/mm 2 =15.31 MPa <[τ]=125MPa 2# 葫芦承受最大弯矩为: M x =Pab/l=240*1000*3.525*0.5/4.025=105093N.m 2# 葫芦最大剪切力为: V= Pa/l =240*1000*3.525/4.025N= 210186 N 横梁承受的弯曲应力σ 1=M x/W x= 105093 *10 3N·mm/(1204* 10 3mm 3)=87.3 N/mm 2 =87.3 MPa <[σ]=215 MPa 横梁承受的剪切应力τ 1=V/A=210186N /(117.84* 10 2mm 2)=17.84N/mm 2 =17.84 MPa <[τ]=125MPa (2)刚度校核: 1# 葫芦最大挠度计算?= Pa 2b 2/( 3EIl ) =240000N*3025 2*1000 2mm 4/(3*2.06*10 7N/mm 2*25646* 10 4 mm 4 *4025mm ) =0.04mm 刚度? /l=0.04/4025=1/100625 <[?] =1/500 ,刚度满足要求 2# 葫芦最大挠度计算?= Pa 2b 2/( 3EIl ) =240000N*3525 2*500 2mm 4/(3*2.06*10 7N/mm 2*25646* 10 4 mm 4 *4025mm ) =0.012mm 刚度? /l=0.012/4025=1/335416 <[?] =1/500 ,刚度满足要求综上所述,钢梁满足使用要求。 6 四、结论: 经以上计算分析,本项目结构钢梁满足使用要求。